Emerg Infect Dis ; 28(12): 2374-2382, 2022 Dec.
Article in English | MEDLINE | ID: covidwho-2311581

ABSTRACT

We investigated a cluster of SARS-CoV-2 infections in a quarantine hotel in Taiwan in December 2021. The cluster involved 3 case patients who lived in nonadjacent rooms on different floors. They had no direct contact during their stay. By direct exploration of the space above the room ceilings, we found residual tunnels, wall defects, and truncated pipes between their rooms. We conducted a simplified tracer-gas experiment to assess the interconnection between rooms. Aerosol transmission through structural defects in floors and walls in this poorly ventilated hotel was the most likely route of virus transmission. This event demonstrates the high transmissibility of Omicron variants, even across rooms and floors, through structural defects. Our findings emphasize the importance of ventilation and integrity of building structure in quarantine facilities.


Subject(s)
COVID-19 , SARS-CoV-2 , Humans , Quarantine , Taiwan/epidemiology , Respiratory Aerosols and Droplets